Huawei SUN2000-(3KTL-10KTL)-M1 Solar Inverter

24 feilkoder dokumentert

2001

High string input voltage

The PV array is not properly configured, with too many PV modules connected in series, causing the PV string open-circuit voltage to exceed the maximum SUN2000 operating voltage. This can damage the inverter.

2002

DC arc fault

Arcing or poor contact exists in the PV string power cables for PV strings 1 and 2 (Cause ID 1) or PV strings 3 and 4 (Cause ID 2). This indicates an electrical safety hazard.

2003

DC arc fault

Arcing or poor contact exists in the PV string power cables for PV1 (Cause ID 1) or PV2 (Cause ID 2). This indicates an electrical safety hazard.

2011

String reverse connection

The polarity of the PV string is reversed (PV1 for Cause ID 1, PV2 for Cause ID 2). This prevents proper power generation and can potentially damage the inverter.

2012

String current backfeed

The number of PV modules connected in series to the PV string is insufficient, resulting in a lower end voltage compared to other parallel strings. This can lead to inefficient operation or potential current backfeed issues.

2021

AFCI self-check failure

The Arc Fault Circuit Interrupter (AFCI) self-check function fails. This indicates a potential malfunction of a critical safety feature designed to detect and mitigate electrical arcs.

2031

Phase wire short-circuited to PE

The impedance of the output phase wire to PE (Protective Earth) is low or the output phase wire is short-circuited to PE. This is a serious electrical safety fault indicating a direct connection between a phase conductor and ground.

2032

Grid loss

A power grid outage has occurred, or the AC circuit is disconnected or the AC switch is off. This prevents the inverter from feeding power to the grid.

2033

Grid undervoltage

The grid voltage is below the lower threshold or the low-voltage duration has lasted for more than the value specified by low voltage ride-through (LVRT). This indicates an unstable or insufficient grid voltage.

2034

Grid overvoltage

The grid voltage exceeds the upper threshold or the high voltage duration has lasted for more than the value specified by high voltage ride-through (HVRT). This indicates an unstable or excessively high grid voltage.

2035

Grid volt. Imbalance

The difference between grid phase voltages exceeds the upper threshold. This indicates an imbalance in the three-phase power grid, which can affect the inverter's stable operation.

2036

Grid overfrequency

The actual power grid frequency is higher than the requirements for the local power grid code. This indicates an exception in the power grid's frequency stability.

2037

Grid underfrequency

The actual power grid frequency is lower than the requirements for the local power grid code. This indicates an exception in the power grid's frequency stability.

2038

Unstable grid frequency

The power grid frequency's actual change rate does not meet the requirements of the local power grid code. This can indicate temporary power grid abnormalities or a persistent issue with grid frequency stability.

2039

Output overcurrent

The SUN2000's transient output current exceeds its upper threshold, triggering protection due to a dramatic drop in power grid voltage or a short-circuited power grid. This indicates an external electrical fault affecting the inverter's output.

2040

Output DC component overhigh

The DC component in the power grid current exceeds the upper threshold. This indicates an issue with the quality of the current being fed into the grid.

2051

Abnormal residual current

The input-to-ground insulation impedance has decreased during the SUN2000 operation. This typically indicates an insulation fault or a temporary issue with external power cabling.

2062

Low insulation resistance

A short circuit exists between the PV array and the ground, or the PV array is in a moist environment with poor insulation. This is a critical safety fault indicating potential electrical leakage.

2063

Cabinet overtemperature

The SUN2000's cabinet temperature exceeds the upper threshold due to poor ventilation, high ambient temperature, or an internal operational issue. This can lead to reduced performance and equipment damage.

2064

Equipment fault

An unrecoverable fault has occurred on a circuit inside the SUN2000, indicating an internal hardware issue. This requires a reset or professional intervention.

2081

Optimizer fault

An optimizer is offline or faulty, preventing proper operation of the PV string optimization. This can lead to reduced power output from the affected strings.

2082

Grid-tied/Off-grid Controller Abnormal

The inverter fails to communicate with the Smart Backup Box or an unrecoverable fault occurs on a circuit inside the Smart Backup Box. This impacts the inverter's ability to operate in grid-tied or off-grid modes.

Grid Failure

Grid Failure

This alarm is reported when the DC input is on but the AC output is off. The SUN2000 cannot operate in grid-tied mode under these conditions.

Low Insulation Resistance

Low Insulation Resistance

This alarm indicates that the insulation resistance of a PV string is low, suggesting a potential short-circuit. The inverter provides a percentage for the possible short-circuit position, with 0% representing the PV- terminal and 100% representing the PV+ terminal. Other percentages indicate a fault on a PV module or cable within the PV string, with a detection precision of ±1 PV module.