Output DC Component Overhigh

Huawei · SUN2000 Solar Inverter

Hva betyr 2040 ?

The DC component of the SUN2000 output current exceeds the specified upper threshold. An excessive DC component can cause transformer saturation in the grid and affect other grid-tied equipment.

Vanlige årsaker

  • The DC component of the SUN2000 output current exceeds the specified upper threshold.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify grid voltage and frequency at the inverter's AC output terminals are stable and within specified operating limits.

  2. 2

    Check inverter grid-tie parameters and local grid code settings, especially those related to DC injection limits, to ensure proper configuration.

  3. 3

    Inspect all AC output cabling and grounding connections from the inverter to the grid for secure termination, absence of corrosion, and physical integrity.

  4. 4

    Monitor the inverter's diagnostic logs and real-time output current data for any other correlating error messages or abnormal waveform characteristics.