Indramat · ECODRIVE Controller
An error was detected during the evaluation of the motor encoder signals, indicating an issue with the encoder feedback. This error typically signifies corrupted or missing encoder pulses, affecting the drive's ability to accurately determine motor position or speed.
Click steps to track your progress.
Inspect the encoder cable for physical damage, proper shielding, and secure connections at both the motor encoder and drive controller ends. Replace the cable if necessary.
Ensure the encoder cable is routed separately from power cables to minimize electromagnetic interference (EMI). Verify proper grounding and shielding.
Check the encoder for proper mounting and connection, ensuring no mechanical play or contamination affects its operation.
If previous steps do not resolve the issue, and assuming the encoder itself is not faulty, consider exchanging the drive controller as per the manual's suggestion for a defective drive.