Motor Rotation Reversed

Kone · Frequency Inverter

Hva betyr 22 ?

This error indicates that slippage due to reversed motor rotation has occurred for more than 0.5 seconds. Specifically, it is recorded if speed feedback from Port A and B on the master control PCB shows values less than -150 mm during upward travel or greater than 150 mm during downward travel, signifying movement in the unintended direction.

Vanlige årsaker

  • Incorrect motor wiring or phase sequence, causing the motor to rotate in the opposite direction than commanded.
  • Malfunction or incorrect connection of speed feedback sensors (e.g., encoder) to Ports A and B on the master control PCB.
  • Mechanical slippage between the motor and the driven load, causing the detected speed feedback to deviate significantly.
  • Incorrect configuration of motor rotation direction in the drive parameters.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the motor's power wiring connections to ensure the correct phase sequence and direction of rotation.

  2. 2

    Check the connections and functionality of the speed feedback device (encoder) to Ports A and B on the master control PCB.

  3. 3

    Inspect the mechanical coupling between the motor and the lift's traction system for any signs of slippage.

  4. 4

    Confirm that the motor rotation direction parameter in the drive settings matches the intended physical direction for upward and downward travel.