Key alarm
Schindler · Easy Altivar ATV310 Drive
Hva betyr A-17 ?
The Key alarm indicates an issue with the display terminal's keypad. This fault is triggered if a key remains pressed for longer than 10 seconds, if the membrane switch is disconnected, or if the display terminal powers on while a key is already depressed.
Vanlige årsaker
- A key on the display terminal is stuck in the pressed position for an extended period (over 10 seconds).
- The membrane switch of the display terminal is disconnected or has failed internally.
- The display terminal was woken up or powered on with one or more keys already pressed.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Inspect the display terminal keypad for any physically stuck keys and gently clean around them to ensure free movement.
- 2
Check the connection of the membrane switch to the display terminal's PCB, ensuring it is properly seated.
- 3
Ensure no keys are pressed when the display terminal is powered on or woken up.
- 4
If the fault persists after checking the keypad, consider replacing the display terminal as the membrane switch or internal components may be faulty.