F001
Precharge
Schindler · Easy Altivar ATV310 Drive
Hva betyr F001 ?
For the ATV310 drive, this fault indicates an issue within the internal DC bus precharge circuit. This typically involves a fault with the charging relay control or damage to the precharge resistor, preventing the DC bus capacitors from charging correctly upon power-up.
Vanlige årsaker
- Charging relay control fault within the drive's precharge circuit
- Charging resistor damaged or failed in the precharge circuit
- Instability or transient issues with the main input supply voltage
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Turn the ATV310 drive off completely, wait for the display to extinguish, and then turn it back on.
- 2
Check the main power input connections to the drive for tightness and correct phase sequencing.
- 3
Verify the stability of the main input supply voltage, checking for sags or swells during power-up.