F002

Unknown drive rating

Schindler · Easy Altivar ATV310 Drive

Hva betyr F002 ?

This ATV310 fault signifies an internal inconsistency where the power card and the stored control card versions are different or incompatible. The drive is unable to correctly identify its own power rating, indicating an internal hardware or firmware mismatch.

Vanlige årsaker

  • Power card and stored control card versions are different or incompatible

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Turn the ATV310 drive off and then back on again after waiting for at least 5 minutes to ensure a full reset.

  2. 2

    Check the input power supply to the drive for stability and ensure correct voltage levels are present.

  3. 3

    Visually inspect the drive for any obvious signs of physical damage or loose connections on internal cards.

  4. 4

    Contact local Schneider Electric representative to address the internal power card and control card version mismatch.