F021

Load short circuit

Schindler · Easy Altivar ATV310 Drive

Hva betyr F021 ?

This ATV310 fault detects a short-circuit condition at the drive's output, impacting the motor or cabling. It can be triggered either at the run command or during a DC injection command, especially if parameter 608 (IGBT Test) is set to 01.

Vanlige årsaker

  • Short-circuit at the drive output terminals (U, V, W)
  • Short circuit detected at the run command or during DC injection command if parameter 608 (IGBT Test) is set to 01

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Disconnect the motor from the ATV310 drive's output terminals.

  2. 2

    Check the cables connecting the drive to the motor for any short circuits (phase-to-phase or phase-to-ground) using a multimeter.

  3. 3

    Test the motor winding insulation resistance with a megohmmeter (megger) to ensure there are no ground faults or inter-phase shorts.

  4. 4

    Verify parameter 608 (IGBT Test) setting; if set to 01, ensure the motor and cabling are correctly installed and checked before attempting to run.

Se alle koder i denne manualen (37)
Verifisert teknisk data. Sist oppdatert: March 2026