Oversetter...
-ObF

Overvoltage During Deceleration

Schneider Electric · Altivar Machine ATV340 Programming

Hva betyr -ObF ?

This fault occurs when the motor generates excessive regenerative energy back into the drive controller's DC bus during rapid deceleration or when driving an overhauling load (e.g., lowering a weight). This rapid increase in DC bus voltage can exceed safe limits and damage the drive's internal components if not dissipated properly.

Vanlige årsaker

  • Deceleration ramp time (Parameter P1-04) set too short for the inertia of the driven load, causing rapid energy regeneration.
  • Overhauling load application (e.g., crane, elevator, high-inertia fan) generating significant regenerative energy back into the DC bus.
  • Braking resistor circuit malfunction (e.g., open resistor, failed braking chopper module), preventing energy dissipation.
  • Drive's internal DC bus capacitors reaching end-of-life, reducing their capacity to absorb regenerative energy and causing voltage spikes.
  • Incorrect overvoltage trip level (Parameter P5-02) set too low, causing premature tripping during normal deceleration.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Increase the deceleration ramp time (Parameter P1-04) by 1-2 seconds and retest the application.

  2. 2

    Measure the resistance of the external braking resistor with a multimeter (power OFF). Compare to its specified value.

  3. 3

    Verify the braking chopper is functioning by measuring voltage across the braking resistor during deceleration (if safely possible).

  4. 4

    If an overhauling load is present, confirm the braking resistor and chopper are correctly sized for the application's regenerative energy.

  5. 5

    Ensure overvoltage trip level (Parameter P5-02) is at its default or appropriate setting (if configurable for specific applications).