-SCF

Motor Short-Circuit

Schneider Electric · Altivar Machine ATV340 Programming

Hva betyr -SCF ?

This fault indicates a short-circuit or ground fault has occurred at the output of the drive controller, either in the motor cables or within the motor itself. This is a critical fault that can severely damage the drive controller's output stage (IGBTs) if power is maintained. Immediate action is required to prevent component failure.

Vanlige årsaker

  • Insulation breakdown in motor power cables (U, V, W) due to abrasion, crushing, or chemical exposure, creating a phase-to-phase or phase-to-ground short.
  • Short-circuit between motor windings or a winding to the motor frame (ground fault) inside the motor stator due to winding degradation.
  • Water ingress into the motor terminal box or cable glands, creating a conductive path between phases or to ground.
  • Internal failure of drive output power components (e.g., IGBTs) causing a direct short at the output terminals.
  • Incorrect motor connection (e.g., delta configuration for a wye-configured motor) causing excessive current and a protective short-circuit trip.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Disconnect motor cables (U, V, W) from the drive output terminals (T1, T2, T3) before proceeding.

  2. 2

    Perform an insulation resistance test (megger) on each motor phase cable to ground and phase-to-phase. Test at 500VDC.

  3. 3

    Measure resistance between motor phases (U-V, V-W, W-U) using a multimeter at the motor terminal box. Expect balanced, low resistance readings.

  4. 4

    Measure resistance from each motor phase to the motor frame ground using a multimeter. Expect an open circuit (infinite resistance).

  5. 5

    If motor and cables test good, measure resistance between drive output terminals (T1, T2, T3) with power OFF. Expect high resistance (internal components).

Se alle koder i denne manualen (13)
Verifisert teknisk data. Sist oppdatert: March 2026