Oversetter...
44
Adjustable current limitation exceeded
SEW Eurodrive · MOVIMOT MM..D With AC Motor DRS
Hva betyr 44 ?
The drive has operated at its set current limit for longer than 500 ms when additional function 2 (adjustable current limitation) is active and the monitoring function is in effect (above 15 Hz). This indicates the motor is drawing too much current.
Vanlige årsaker
- Drive operating at the current limit for more than 500 ms while additional function 2 (adjustable current limitation) is active and monitoring is enabled (above 15 Hz)
- Current limit setting (Imax % of IN) via switch f2 on S2 is too low for the application's load
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the current limit setting using switch f2 on S2 (detent settings 0-10 correspond to 90-160% of IN) and adjust if appropriate for the application
- 2
Reduce the load on the drive to prevent current limit activation
- 3
Verify the minimum frequency (2 Hz for RS-485 control) and setpoint f2 (5 Hz for binary control) are correctly configured
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: SEW Eurodrive MOVIMOT MM..D With AC Motor DRS