Oversetter...
81
Start condition error
SEW Eurodrive · MOVIMOT MM..D With AC Motor DRS
Hva betyr 81 ?
The motor could not be supplied with the correct amount of current during its pre-magnetizing time, preventing a proper start-up sequence. This often points to a mismatch between inverter and motor ratings or issues with cabling.
Vanlige årsaker
- Rated motor power is too small compared to the rated inverter power
- Motor cable cross section is too small, impeding current delivery
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the connection between the MOVIMOT® inverter and motor for proper sizing and cable integrity
- 2
Verify the rated motor power is appropriately matched with the rated inverter power
- 3
Reset the error by switching off the DC 24 V supply voltage
- 4
Reset the error via the control system or dedicated reset function
Verifisert teknisk data. Sist oppdatert: March 2026