89

Thermal overload of brake coil or brake coil defective/incorrectly connected

SEW Eurodrive · MOVIMOT MM..D With AC Motor DRS

Hva betyr 89 ?

The brake coil has experienced a thermal overload, is defective, or is connected improperly. This can lead to braking issues, potential drive damage, and requires inspection of the brake system.

Vanlige årsaker

  • Ramp time set too short, causing frequent or prolonged brake engagement and overheating
  • Defective brake coil
  • Incorrect brake coil connection
  • Mismatched drive (brake coil) and MOVIMOT® frequency inverter combination signaled shortly after first enable
  • Incorrect setting of DIP switch S1/6 for combinations of MOVIMOT® and motor with a lower power rating

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Increase the set ramp time

  2. 2

    Perform brake inspection (refer to 'Inspection and maintenance of the brake' section in the manual)

  3. 3

    Check the brake coil connection and correct if necessary

  4. 4

    Check the combination of the drive (brake coil) and MOVIMOT® frequency inverter for compatibility

  5. 5

    Check the setting of DIP switch S1/6 for combinations of MOVIMOT® and motor with one lower power rating

  6. 6

    Reset the error by switching off the DC 24 V supply voltage