Option missing
SEW Eurodrive · MOVITRAC 07B System
Hva betyr F36 ?
An option card is either incorrect, missing, or has incompatible settings for its setpoint source, control signal, or operating mode. This fault indicates a configuration mismatch or hardware absence, leading to an immediate switch-off with inhibit.
Vanlige årsaker
- Installation of an unsupported or incorrect type of option card
- Setpoint source, control signal source, or operating mode parameters are incompatible with the installed option card
- Required option card (e.g., FBG11B, FIO12B, FIO21B) is not present
- Front module FIO21B is not supplied with power
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Install the correct type of option card for the application.
- 2
Verify parameters for setpoint source, control signal source, and operating mode are compatible with the installed option card.
- 3
Check parameters P120 and P121 for general option card configuration.
- 4
If FBG11B is used, check parameter P121. If FIO12B is used, check P120 and P642.
- 5
If FIO21B is installed, set parameter P808 to "On" or supply the basic unit with external 24V.