External Fault
Yaskawa · VS-616G5 Variable Speed Drive
Hva betyr EF7 ?
This fault indicates that an external protective device or interlock connected to a specific digital input (corresponding to EF7) has been activated, triggering a trip in the inverter. The specific cause depends on the external device wired to that input. This is a safety feature to stop the drive based on external process conditions, preventing damage to the system or injury.
Vanlige årsaker
- Auxiliary contact of a motor starter or contactor connected to EF7 has opened, indicating a fault downstream.
- Wiring damage or poor connection between the auxiliary contact and the digital input assigned as EF7 (e.g., S7).
- Mechanical malfunction of the external device's auxiliary contact.
- Parameter misconfiguration (e.g., P0-10) for the digital input function, leading to an incorrect fault trip.
- Electrical noise on the control circuit causing a momentary false trip on the EF7 input.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Identify the external device (e.g., motor contactor, thermal overload relay) whose auxiliary contact is wired to EF7 (S7).
- 2
Check the operational status of the external device; ensure it is energized and not tripped.
- 3
Measure the voltage between inverter terminal S7 and SC to confirm the input signal's level.
- 4
Inspect wiring integrity from the auxiliary contact to the S7 terminal for breaks, shorts, or loose connections.
- 5
Use a multimeter to verify the continuity of the external device's auxiliary contact when it is in its expected non-tripped state.