0x80EA
Expansion Rack Starting Word Address Exceeded
Omron · CJ-series CJ2 CPU Unit
What does 0x80EA mean?
An Expansion Rack's starting word address exceeds CIO 0901, preventing the CPU from correctly addressing the I/O for the rack. The corresponding bit in A409.00 to A409.03 (Racks 0 to 3) will be turned ON, indicating the affected rack.
Common Causes
- The first word setting for the Expansion Rack is configured above CIO 0900.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Check the first word setting for the Rack indicated by A409.00 to A409.03.
- 2
Using a Programming Device (e.g., CX-Programmer), change the setting to a valid word address below CIO 0900.
Verified technical data. Last updated: March 2026
Related Faults
Source: Omron CJ-series CJ2 CPU Unit