015
Multi-step Speed Reference 0 Exceeds Upper Limit
Omron · MX2 Inverter
What does 015 mean?
This warning occurs if the frequency set for Multi-step speed reference 0 (A020) or the output frequency setting (F001) is higher than the configured frequency upper limit (A061). This creates a logical conflict in the drive's speed constraints, as a programmed speed is above the allowed maximum.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Increase A061 (Frequency upper limit) to accommodate the required Multi-step speed reference 0 if higher speeds are valid for the application.
Source: Omron MX2 Inverter