E35
Thermistor Trip
Omron · MX2 Inverter
What does E35 mean?
This fault is activated when an external thermistor, connected to the inverter's input terminals [5] and [L], detects that the motor temperature has exceeded a safe limit (typically above 3 kΩ ±10%). The inverter trips and turns off its output to prevent motor overheating and damage.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Verify the thermistor's resistance value at ambient temperature; if it's open-circuited or out of range, replace it.
- 4
Ensure the motor load and operating conditions are within its rated thermal limits to prevent chronic overheating.
- 5
Clear the error by pressing the Stop/Reset key on the inverter keypad after the motor has cooled sufficiently.