E36

Braking Error

Omron · MX2 Inverter

What does E36 mean?

This fault occurs during brake control operation if the inverter fails to receive the braking confirmation signal within the specified time (b124) after a brake release, or if the output current doesn't reach the brake release current (b126) during the brake wait time (b121). It indicates a problem with the brake's operation or its feedback to the inverter.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Review and adjust the brake control parameters: b120 (Brake control selection), b121 (Brake wait time for release), b124 (Brake wait time for confirmation), and b126 (Brake release current).

  2. 4

    Measure the actual output current during brake operation to ensure it meets the b126 setting required for brake release.

  3. 5

    If the brake mechanism is faulty or worn, repair or replace the brake components.

Source: Omron MX2 Inverter