A408.08 to A408.15

Basic I/O Unit Error - Rack Number

Omron · SYSMAC CJ2 CPU Unit

What does A408.08 to A408.15 mean?

When an error occurs in a Basic I/O Unit, this word stores the Rack number (00 to 03 hexadecimal) where the error was detected. The CPU Unit continues operating, but the ERR/ALM indicator on the front of the CPU Unit will flash. The presence of this error is also indicated by A402.12 being ON.

Common Causes

  • Hardware malfunction within a Basic I/O Unit located on the indicated rack
  • Faulty backplane or power supply on the identified rack
  • Issues with the expansion cable connecting to the problematic rack

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Identify the problematic Rack by checking the rack number indicated in A408.08 to A408.15

  2. 2

    Inspect all Basic I/O Units on the identified rack for proper seating and connection

  3. 3

    Check the integrity of the expansion cables connecting to the identified rack

  4. 4

    Verify the power supply to the identified rack is stable and within specifications

  5. 5

    Consider swapping Basic I/O Units between slots on the identified rack to isolate the faulty component