A528.02
RS-232C Port Parity Error
Omron · SYSMAC CJ2 CPU Unit
What does A528.02 mean?
This flag turns ON when a parity error occurs during RS-232C communication. This indicates a data transmission integrity issue at the RS-232C port. This error flag is valid in Serial Gateway mode.
Common Causes
- Incorrect parity settings configured on the RS-232C port or the connected device
- Noise or interference on the RS-232C communication line
- Faulty RS-232C cable or connector
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the parity setting for the RS-232C port in the PLC's communication parameters matches the connected device's settings
- 2
Inspect the RS-232C cable for damage or loose connections
- 3
Measure voltage levels on the RS-232C communication lines to check for noise or signal integrity issues
- 4
Restart the RS-232C port by turning ON the Serial Port Restart Bit (A526.00) from OFF to ON
Verified technical data. Last updated: March 2026