400
MOTOR OVERLOAD FAULT
Otis · DSD 412 DC Elevator Drive
What does 400 mean?
The drive has delivered excessive motor amps for a significant period of time. This fault does not automatically shut down the drive, but is annunciated via the ALARM relay output K2.
Common Causes
- Improper setup of parameters #83 and #84.
- Dragging elevator brake.
- Weakened motor field.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Refer to parameters #83 and #84 for proper setup and verification.
- 2
Check for a dragging elevator brake.
- 3
Check the motor field strength.
Verified technical data. Last updated: March 2026