413

FIELD CURRENT TRACKING FAULT

Otis · DSD 412 DC Elevator Drive

What does 413 mean?

The actual field current is failing to track the field current command by more than F192 (default = 0.05PU) for 5 seconds. This is not a shutdown fault, but a warning.

Common Causes

  • Incorrect AC voltage on AC1 and AC2.
  • Drives not using correct self-tune values.
  • Field response set incorrectly.
  • Failing to track field current command by more than F192 for 5 seconds.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check AC voltage on AC1 and AC2; it should typically be 1.5 to 2.5 times VACmin where VACmin = VDC/0.9 or (Full Fld Amps * Field resistance)/0.9.

  2. 2

    Verify that the drive is using correct self-tune values and/or field response settings.

  3. 3

    Monitor F620 (Fld Trkg Diff); it should be less than F192.

  4. 4

    Adjust F192 ('F413 Detect Level') to a higher value if necessary, but observe caution prior to doing this.