905
FIELD LOSS FAULT
Otis · DSD 412 Elevator System
What does 905 mean?
The field current feedback has dropped below 80% of the expected current during specific operating conditions: Field Weakening Mode (Top speed, #49), Full Field Mode (Accel or Decel, #50), or Standing Field Mode (not running, #53). This fault will shut down the drive.
Common Causes
- Open circuit failure of motor field or motor field wiring.
- Hardware failure of motor field control circuitry.
- Loss of power or incorrect phasing to the Field Rectifier.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Check the motor field and motor field wiring for an open circuit.
- 2
Inspect motor field control circuitry for hardware failure.
- 3
Verify power supply and phasing to the Field Rectifier.
Verified technical data. Last updated: March 2026
Related Faults
Source: Otis DSD 412 Elevator System