911
SHORTED SCRS/DOUBLER FAULT
Otis · DSD 412 Elevator System
What does 911 mean?
One of the SCR/Doubler packs has a short circuit between the SCRs. This condition is checked only upon request through the PCU #998 Diagnostics CDU function. The optional handheld PCDU can identify which specific SCR pair is faulty. This fault requires a DSD Power Down.
Common Causes
- Short circuit between SCRs in an SCR/Doubler pack.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Use the PCU #998 Diagnostics CDU function to identify the shorted SCR pair.
- 2
Replace the faulty SCR/Doubler pack.
Verified technical data. Last updated: March 2026
Related Faults
Source: Otis DSD 412 Elevator System