Fd1
Closed Damper 1 Fault
Schindler · Altivar 212 Variable Frequency Drive
What does Fd1 mean?
This fault indicates that the damper is locked in a closed position, preventing proper air flow or ventilation, which can lead to overheating or process issues. The drive typically locks in this fault mode.
Common Causes
- Damper is locked in closed position.
- Incorrect settings for damper feedback or relay control (F130, F132, F583).
Repair Steps & Checklist
Click steps to track your progress.
- 1
Set parameter [Damper flt behavior] (F583) to 0 (No fault).
- 2
Check the FL relay connection (FLA/FLB terminals) for proper wiring.
- 3
Verify the relay configuration using parameters F130 ([RY Relay Function 1]) and F132 ([FL Relay Function]).
Verified technical data. Last updated: March 2026