OC3P

Short Circuit or Ground Fault During Constant Speed

Schindler · Altivar 212 Variable Frequency Drive

What does OC3P mean?

This fault indicates a short circuit or ground fault condition detected while the Altivar 212 drive is operating at a constant speed, potentially also due to a malfunctioning cooling fan.

Common Causes

  • Short circuit or ground fault during constant speed operation.
  • The drive cooling fan is not working.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Use a 1000 V testing tool (megger) to check the motor and motor cables for ground faults.

  2. 2

    Check the operation of the drive's cooling fan.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026