UP1
Undervoltage
Schindler · Altivar 212 Variable Frequency Drive
What does UP1 mean?
This fault indicates that the input voltage to the Altivar 212 drive is too low, potentially causing instability or improper operation. This can lead to a drive trip to prevent damage.
Common Causes
- The input voltage to the drive is too low.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Measure the input voltage at the drive terminals (R/L1, S/L2, T/L3) and rectify the supply trouble.
- 2
Select the correct setting for parameter F627 ([Undervolt detect.]).
- 3
Enable catch on the fly function (F301).
- 4
Set parameter F302 ([Supply loss behav.]) to 2 (Freewheel).
Verified technical data. Last updated: March 2026