F030

Undervoltage

Schindler · Easy Altivar ATV310 Drive

What does F030 mean?

The Undervoltage fault occurs when the line supply voltage to the drive is too low or experiences a transient dip. This can lead to unstable drive operation or shutdown to protect internal components.

Common Causes

  • Input line supply voltage is below the specified operating range for the drive.
  • A transient voltage dip occurred on the power supply line.
  • Loose or corroded power connections to the drive's input terminals.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the incoming line supply voltage at the drive's input terminals and compare it to the drive's nominal voltage.

  2. 2

    Inspect all power connections to the drive for proper termination and tightness.

  3. 3

    Review the Undervoltage menu (607-) parameters (page 106), especially Undervoltage detected fault management (607.0) and Undervoltage prevention (607.1), to ensure appropriate settings for the application.

  4. 4

    Monitor the line voltage for transient dips using a power quality analyzer.

Browse all codes in this manual (37)