SOF

Overspeed

Schneider Electric · Altivar 312 Variable Frequency Drive

What does SOF mean?

The motor speed has exceeded its commanded or permissible limit, often due to an unstable control loop, an excessive regenerative load, or a mechanical runaway condition. This fault is critical as it can lead to mechanical damage to the driven equipment, create safety hazards, and result in a complete loss of control over the motor.

Complete Troubleshooting Guide

  1. 1

    Check the motor's mechanical system for any free-running conditions or loss of load.

  2. 2

    Review the drive's gain and stability parameters to ensure the control loop is stable and appropriately tuned for the application.

  3. 3

    Add a braking resistor (and braking unit) if the application involves high inertial loads or frequent rapid decelerations that cause regenerative energy feedback.

  4. 4

    Verify that the motor and drive are correctly sized for the application's torque and speed requirements.