OtFL

PTC Fault (Motor Overheating)

Schneider Electric · Altivar Machine ATV320 Variable Speed Drive

What does OtFL mean?

A motor overheating detected error from a PTCL (Positive Temperature Coefficient Logic) standard product. This indicates that the PTC thermistor embedded in the motor windings has exceeded its trip temperature, signaling a critical motor overheating condition. Continuous operation will severely damage the motor.

Complete Troubleshooting Guide

  1. 1

    Allow the motor to cool down completely.

  2. 2

    Check the motor's mechanical load and reduce it if excessive.

  3. 3

    Verify proper motor ventilation and ensure cooling fins are clean and unobstructed.

  4. 4

    Check the PTC probe wiring for continuity, correct connection to the drive, and proper isolation.

  5. 5

    Ensure the motor's rated current and operating parameters are correctly configured in the drive.