Overvoltage During Deceleration
Schneider Electric · Altivar Machine ATV340 Programming
What does -ObF mean?
This fault occurs when the motor generates excessive regenerative energy back into the drive controller's DC bus during rapid deceleration or when driving an overhauling load (e.g., lowering a weight). This rapid increase in DC bus voltage can exceed safe limits and damage the drive's internal components if not dissipated properly.
Complete Troubleshooting Guide
- 1
Increase the deceleration ramp time in the drive controller's settings to allow for a slower, controlled stop, reducing regenerative energy.
- 2
If the load is highly inertial or overhauling, install an external braking resistor (and braking unit, if required) to dissipate the regenerative energy generated by the motor.
- 3
Consider activating the 'brA' (Braking Control) function in the drive's parameters if supported and compatible with the application, as described on page 63, to optimize regenerative energy handling.