F49
DC Over Voltage
Schneider Electric · XW Pro NA Operation Guide
What does F49 mean?
This Escalating Automatic Fault occurs if the DC voltage exceeds the High Battery Cut Out (HBCO) setting. It can also be triggered if batteries are disconnected at the DC breaker while the XW Pro is charging, leading to potential overcharging or damage to connected equipment.
Complete Troubleshooting Guide
- 1
Clear the fault and attempt restart.
- 2
Ensure battery voltage is below HBCO at XW Pro terminals.
- 3
Check all other charging source outputs and battery cables.
- 4
Ensure that batteries are connected, or that your DC source is regulated below your high battery cut out.
- 5
Increase your Hi Batt Cut Out setting.