91
Communication timeout bus module – MOVIMOT®
SEW Eurodrive · Drives
What does 91 mean?
The communications link between the fieldbus interface (MFP/MFI) and the MOVIMOT® inverter is interrupted or experiences a timeout. This system fault is signaled to the PLC as error code 91 dec via the diagnostics channel or status words, and typically triggers a steady 'SYS-F' LED light on the fieldbus interface.
Common Causes
- Interrupted or faulty electrical communication link between the fieldbus interface (MFP/MFI) and the MOVIMOT® inverter.
- Missing 24 V supply to the MOVIMOT® inverter.
- Maintenance switch on the field distributor is set to OFF.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Check and re-establish the electrical communication link between the fieldbus interface (MFP/MFI) and the MOVIMOT® inverter (e.g., verify connections at terminals RS+ and RS-).
- 2
Verify the 24 V electronics supply voltage to the MOVIMOT® inverter.
- 3
Check the setting of the maintenance switch on the field distributor to ensure it is in the ON position.
Verified technical data. Last updated: March 2026