Lag Error
SEW Eurodrive · MOVIDRIVE compact MCF/MCV/MCS4_A
What does 42 mean?
Immediate switch-off because the actual position or speed of the motor is lagging too far behind its setpoint. Possible causes include an incorrectly connected encoder, overly short acceleration ramps, a P component of the positioning controller that is too small, incorrectly set speed controller parameters, a lag fault tolerance value that is too small, or mechanical binding in the system.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Set the P component (proportional gain) of the positioning controller to a higher value.
- 4
Reset or finely tune speed controller parameters.
- 5
Increase the lag fault tolerance value (e.g., P703, P704 for positioning tolerance).
- 6
Check the wiring of the encoder, motor, and mains phases.