07
DC link overvoltage
SEW Eurodrive · MOVIDRIVE compact System
What does 07 mean?
The DC link voltage has exceeded its permissible maximum limit, often caused by excessive regenerative power generated during braking, or potentially a ground fault. This triggers an immediate switch-off to protect the inverter's sensitive electronic components from damage.
Complete Troubleshooting Guide
- 1
Extend deceleration ramps to allow for a more gradual energy dissipation during braking.
- 2
Check the supply cable connection to the braking resistor to ensure it is secure and functional.
- 3
Verify the technical data and functionality of the braking resistor to ensure it can absorb regenerative energy.
- 4
Thoroughly check for any ground faults within the system that could contribute to overvoltage conditions.