6.8.0.0
Parameter Channel Data Length Mismatch
SEW Eurodrive · MOVIDRIVE compact System
What does 6.8.0.0 mean?
During a write service via the parameter channel, an incorrect data length was specified (other than 4 data bytes). This error is generated by the fieldbus card's communication software and indicates a mismatch between the expected data size and the actual data provided for a parameter. This prevents correct parameter configuration.
Complete Troubleshooting Guide
- 1
Check bits 4 and 5 for the data length in the management byte of the parameter channel configuration.
- 2
Verify the write service parameters in the master's communication program to ensure they align with the expected 4-byte data length for the specific parameter being configured.