47

CAN Communication Timeout

SEW Eurodrive · MOVIFIT SC

What does 47 mean?

This fault indicates a timeout in the cyclical communication over the CAN bus, meaning the unit is not receiving expected data from, or sending data to, another device on the CAN network within the specified time window. This can interrupt critical control and data exchange, leading to system halts, unpredictable behavior, or loss of synchronized operation. It's often related to wiring, termination, baud rate, or configuration issues on the bus, and can cause significant process downtime.

Complete Troubleshooting Guide

  1. 1

    Check the CAN bus cabling for continuity, shorts, proper shielding, and ensure correct termination resistors are installed at both ends of the bus.

  2. 2

    Verify that the baud rate and other CAN communication parameters (e.g., node IDs) are correctly configured and consistent across all devices on the network.

  3. 3

    Ensure all devices on the CAN bus, including the master controller, are powered on, functional, and actively participating in communication.

  4. 4

    Monitor the CAN bus activity using a diagnostic tool (e.g., a CAN bus analyzer) to identify communication dropouts, conflicts, or bus errors.