F01773
CU Safety Test Stop Fault
Siemens · DAsl Diagnostics and Alarms
What does F01773 mean?
A safety test stop fault has occurred on the Control Unit (CU) side, specifically indicating that the expected states of the Digital Outputs (DOs) were not fulfilled during a safety test. This means the external readback signal was not set correctly for a given test stop state (e.g., state 7), where an expected value was not observed. This issue compromises the validation of safety functions.
Complete Troubleshooting Guide
- 1
Check the wiring of the F-DOs (Fail-Safe Digital Outputs) and their associated readback signals.
- 2
Restart the test stop procedure to attempt to clear the fault and re-evaluate the safety circuit.
- 3
If multiple test stop faults exist, clearing the current one will allow the next queued fault to be signaled for diagnosis.