F06922
Braking resistor phase failure
Siemens · DCM
What does F06922 mean?
This fault indicates a detected phase failure in one of the braking resistors. Depending on the fault value (U, V, or W), a specific phase's feeder cable may be open or disconnected. This can impair the drive's ability to dissipate regenerative energy, potentially leading to overvoltage faults or control issues.
Complete Troubleshooting Guide
- 1
Visually inspect the feeder cables for any signs of physical damage or insulation degradation.
- 2
Use a multimeter to check the continuity and resistance of each feeder cable to the braking resistors.
- 3
Ensure all cable connections to the braking resistors and the drive are secure and free of corrosion.