F07016

Drive: Motor temperature sensor fault

Siemens · DCM

What does F07016 mean?

An error was detected during the evaluation of the motor temperature sensor (configured in p0601). Possible causes include a wire breakage (KTY: R > 2120 Ohm), the sensor not being connected, or a measured resistance that is too low due to a short circuit (PTC: R < 20 Ohm, KTY: R < 50 Ohm). If alarm A07015 was present, this fault was output after the timer p0607 expired, indicating a prolonged issue.

Complete Troubleshooting Guide

  1. 1

    Ensure that the motor temperature sensor is connected correctly and securely to the drive's input terminals.

  2. 2

    Check the parameterization of the motor temperature sensor type (p0601) to ensure it matches the actual sensor installed.

  3. 3

    For induction motors, if temperature monitoring is not critical or desired for the application, deactivate the temperature sensor fault by setting parameter p0607 = 0.