207016
Motor Temperature Sensor Fault
Siemens · FC1765DC Controller
What does 207016 mean?
A critical error was detected during the evaluation of the motor temperature sensor (configured via p0600 and p0601). This fault is typically issued if Alarm A07015 persists beyond the configured time in p0607, indicating a sustained issue such as wire breakage, disconnected sensor, or out-of-range resistance values (e.g., KTY: R > 1630 Ohm or R < 50 Ohm, PTC: R < 20 Ohm).
Complete Troubleshooting Guide
- 1
Ensure the temperature sensor is connected correctly to the drive.
- 2
Review and correct the parameterization for p0600 (sensor type) and p0601 (sensor configuration).
- 3
For induction motors, if the sensor is not critical for safety, consider de-activating the temperature sensor fault by setting p0607 = 0 to bypass this check.