Brake control defective
Siemens · SINAMICS G120 Safety Functions
What does F01630 mean?
The motor holding brake control is malfunctioning, posing a risk of uncontrolled motor movement. This can stem from an incorrect p1278 setting, disconnected or interrupted brake cables, a ground fault, or a short-circuit in the brake winding. A fault in the Safe Brake Relay, Control Unit, or Power Module could also be the cause.
Complete Troubleshooting Guide
- 1
Based on fault value r0949, check parameter p1278, inspect brake connections, and test for cable interruptions or ground faults (fault values 10, 11).
- 2
Check for a short-circuit in the brake winding (fault values 20, 30, 31, 40).
- 3
Investigate the Safe Brake Relay, Control Unit, or Power Module for faults (fault value 50).
- 4
Select STO, then deselect it again to try clearing the fault.