F01658

PROFIsafe telegram number unsuitable

Siemens · SINAMICS G120 Safety Functions

What does F01658 mean?

The PROFIsafe telegram number configured in p60022 is not suitable for the enabled safety functions. This indicates an inconsistency in PROFIsafe communication setup, which can prevent safe data exchange and lead to safety function failures.

Complete Troubleshooting Guide

  1. 1

    If PROFIsafe is not enabled (p9601.3 = 0), ensure no PROFIsafe telegram is selected in p60022.

  2. 2

    If PROFIsafe is enabled (p9601.3 = 1), select a suitable PROFIsafe telegram in p60022.

  3. 3

    If transfer of F-DI via PROFIsafe is selected (p9501.30 = 1), ensure telegram 900 is selected in p60022.