F01663

Copying the SI parameters rejected

Siemens · SINAMICS G120 Safety Functions

What does F01663 mean?

The attempt to copy Safety Integrated (SI) parameters was rejected. This can happen if p9700 is not 0, or if safety functions (p9501, p9601) are active, preventing critical parameter changes. This can lead to an inconsistent or un-saved configuration, especially after modifying safety settings.

Complete Troubleshooting Guide

  1. 1

    Set parameter p9700 = 0.

  2. 2

    Check if p9501 ≠ 0 and/or p9601 ≠ 0; if so, correct both parameters.

  3. 3

    Start the copy function again by entering the corresponding value into p9700.