A01696
Switch-on is inhibited
Siemens · SINAMICS G120 Variable Speed Drive
What does A01696 mean?
The drive is unable to switch on and remains in the READY state because its start is inhibited. This can be caused by a deactivated gate driver, an active safety function such as Safe Torque Off (STO), Safe Stop 1 (SS1), or Safe Limited Speed (SLS), or another inhibit condition, preventing motor operation.
Complete Troubleshooting Guide
- 1
Verify that no safety functions (STO, SS1, SLS) are currently active and inhibiting the drive's start.
- 2
Check the status of the gate driver to ensure it is enabled and operational.
- 3
Examine the inhibit bit (r0052.6) in the drive's status words to identify the specific reason for the start inhibition.