A01698
Safety commis./reset act.
Siemens · SINAMICS G120 Variable Speed Drive
What does A01698 mean?
The safety reset or safety commissioning process is currently active, indicated by parameter p0010 = 95. This prevents normal drive operation until the safety procedure is properly concluded, ensuring that all safety configurations are finalized and verified for safe machine control.
Complete Troubleshooting Guide
- 1
Complete the safety commissioning by setting parameter p3900 to 10 (accept changes) or 11 (discard changes).
- 2
If a safety reset is in progress, wait for the process to fully complete before attempting further operations.
- 3
Review the safety parameters to ensure they are configured as desired for the application.