F00061

Par Cl. MMC-PS not fitted Fault

Siemens · SINAMICS G120 Variable Speed Drive

What does F00061 mean?

The parameter cloning process using the MMC-PS (Memory Card Parameter Save) has failed due to various reasons, including an incorrectly formatted or missing MMC-PS, an inability to write to the MMC, or a corrupted cloning file. This prevents successful transfer of drive parameters, impacting drive configuration and operation.

Complete Troubleshooting Guide

  1. 1

    Ensure the correct type of MMC-PS is fitted and properly formatted (FAT12 or FAT16).

  2. 2

    Verify the MMC is not full; if necessary, format it to FAT16 and retry.

  3. 3

    Confirm the clone file (`Clone00.bin`) is correctly named and located in the `/USER/SINAMICS/DATA` directory.

  4. 4

    If the file is inaccessible or corrupted, recreate the clone file from a known good source and attempt the cloning process again.