F00070
PLC setpoint fault
Siemens · SINAMICS G120 Variable Speed Drive
What does F00070 mean?
The drive is not receiving setpoint values from the PLC (Programmable Logic Controller) within the configured telegram off time. This indicates a communication issue or incorrect timing, causing the drive to lose its command reference and cease controlled operation, impacting automation sequences.
Complete Troubleshooting Guide
- 1
Review and adjust parameter p2040, which defines the monitoring time for PLC telegrams, to an appropriate value to prevent premature timeouts.
- 2
Acknowledge the fault in the drive's control interface.
- 3
If the fault persists after checking communication and p2040, consider replacing the inverter control unit, as it might indicate an internal communication hardware issue.