A30057

Power unit: Line asymmetry

Siemens · SINAMICS G120C Variable Speed Drive

What does A30057 mean?

Frequencies detected on the DC link voltage suggest line asymmetry or the failure of a line or motor phase. If this alarm persists, it will eventually trigger fault F30011 after a specific duration. This condition causes imbalanced currents, increased losses, and premature component wear, and if unresolved, will lead to a drive trip, interrupting operation.

Complete Troubleshooting Guide

  1. 1

    Thoroughly inspect all line phase connections for secure contact.

  2. 2

    Verify the integrity of all motor feeder cable connections.

  3. 3

    If no phase failure is found, reduce the drive's output power to prevent triggering fault F30011.